Population Equivalents (PE)


In order to design pipe network, pump stations and sewage treatment plants, estimates need to be made of the volumetric flow rate which will be expected to be carried, pumped and treated.

Such flow rates are measured in cubic metres per second and need to be calculated for both existing land use and for expected future development.

There are many methods for calculating expected flow rates. One method is to calculate a design parameter called the "population equivalent" (PE) of a catchment and convert this to a flow rate.

The PE is an estimate of the usage made of sewage facilities. It is not a measure of population.

For residential areas the population equivalent is calculated as five per dwelling and is a direct measurement of the population in an area.

However for commercial areas it is calculated from the floor area, which is considered to be proportional to the number of people using a premises during the day. In this case it does not reflect the population living in an area.

The following table shows how the PE is calculated.

Type of Establishment Population Equivalent
Residential 5 per house
Commercial 3 per 100m2 area
Educational Institutions  
- Day Schools 0.2 per student
- Residential Schools 1 per student (residential)
Hospitals 4 per bed
Hotels 4 per room
Factories 0.3 per employee
Market (Wet Type) 3 per stall
Market (Dry Type) 1 per stall
Petrol Stations 18 per service bay
Bus Terminal 4 per bus bay
Taxi Terminal 4 per taxi bay
Mosque 0.5 per person
Church or Temple 0.2 per person
Stadium 0.2 per person
Swimming Pool or Sports Complex 0.5 per person
Public Toilet 16 per WC (water closet)
Airport 0.2 per passenger/day
Airport 0.3 per employee
Laundry 10 per machine
Prison 1 per person
Golf Course 20 per hole


The PE may be converted to a flow rate using a simple formula such as set out in Malaysian Standards 1228 (MS1228).